Browse Categories

ALTRONIX EFLOW104NB, PS, 1 OUT, 24VDC @ 10A, AUX OUT, FAI, LINQ2 READY, BOARD

Item #: AL-EFLOW104NB

Product Info

78223994985, ALEFLOW104NB
ALTRONIX CORPORATION
EFLOW104NB

TWO (2) OUTPUT POWER SUPPLY/CHARGER WITH FIRE ALARM DISCONNECT – 24VDC AT 10 AMP MAX ADDITIONAL SEPARATE 1 AMP AUX. CLASS 2 RATED POWER-LIMITED OUTPUT AC & BATTERY MONITORING LOW POWER SHUTDOWN OVER VOLTAGE PROTECTION (OVP) 115VAC INPUT UL RECOGNIZ

Altronix eFlow104NB UL Listed Sub-Assembly power supply/charger converts a 120VAC, 60Hz input into a single 24VDC output. It also offers a suite of features that includes fire alarm disconnect, overvoltage protection, and low power disconnect which prevents deep discharge of stand-by batteries.

Input

  • Voltage: 120VAC 60Hz, 4.5A max.
  • Input Fuse: 6.3A/250V
  • Removable AC input terminal block to facilitate installation and wiring.

Output

  • 24VDC output.
  • 10A continuous supply current.
  • Aux. power-limited output rated @ 1A (unswitched).
  • Over Voltage Protection.
  • Filtered and electronically regulated outputs.

Battery Charging

  • Built-in charger for sealed lead acid or gel type batteries.
  • Automatic switch over to stand-by battery when AC fails.
  • Transfer to stand-by battery power is instantaneous with no interruption.
    (Batteries are sold separately).

Fire Alarm Disconnect

  • Supervised Fire Alarm disconnect (latching or non latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.

Supervision

  • AC fail supervision (form “C” contacts).
  • Notification trigger is selectable for 30 seconds (factory set) or 2 hours.
  • Battery fail & presence supervision (form “C” contacts).
  • Low power shutdown. Shuts down DC output terminals if battery voltage drops below 80% of nominal. Prevents deep battery discharge.

Electrical
Temperature:

  • Operating: 0° C to 49° C (32° F to 120° F).
  • Storage: – 20° C to 70° C ( – 4° F to 158° F).
  • Relative Humidity: 85% +/- 5%.
  • BTU/Hr. (approx.): 123 BTU/Hr.
  • System AC input VA requirement: 540VA.

Visual Indicators

  • Green AC Power LED indicates 120VAC present.
  • AC input and DC output LED indicators.

Additional Features

  • Short circuit and overload protection.