Browse Categories

ALTRONIX T2PDK77F24S, 24-DR PDK RED ACCESS/PWR INTEGRATION KIT-Trove2PD2 W/ (2) eFlow104NB, (2) ACMS12, VR6, (2) PDS8.

PDK 20A 24DR SYS/FUSE
Item #: AL-T2PDK77F24S

Product Info

ALT2PDK77F24S
ALTRONIX CORPORATION
T2PDK77F24S

PDK 20A 24DR SYS/FUSE

AccessNsite, Avigilon, BadgePass, BluBox, Feenics, Genetec, Identicard, IMRON, Johnson Controls, Kastle, Keri Systems, Lenel/S2, LockState, Maxxess, Midpoint Security, NLSS, Open Options, Panasonic Video Insight, Quintron, RS2, S2 Security, Schneider Electric, Vanderbilt

Two (2) eFlow104NB Power Supply/Chargers
Input

  • Voltage: 120VAC, 60Hz, 9A.
  • Main Fuse: 6.5A / 250V.
    Output
  • Voltage: 24VDC @ 10A.
  • Auxiliary: 1A (unswitched).
  • Other: Overvoltage protection. Filtered and regulated.
    Battery Charging
  • Capacity: 12VDC/12AH (2 within enclosure); 40 AH / 65 AH (requires separate enclosure)
  • Type: Sealed lead acid or gel type
  • Failover: Upon AC loss, instantaneous
    (Batteries are sold separately).

Fire Alarm Disconnect

  • Supervised: Latching or non-latching.
  • EOL: 10K Resistor.
    Supervision
  • AC Failure: Form “C” contacts.
  • Battery: Form “C” contacts.
  • Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
    Indicators LED
  • AC Input: 120VAC is present.
  • DC Output: Powered.
  • Battery: Discharged or not connected.

Two (2) ACMS12 Dual Input Access Power Controllers
Input

  • Voltage: First ACMS12 – 24VDC from first eFlow104NB.
  • Voltage: Second ACMS12 – 24VDC from second eFlow104NB.
  • Input Fuse: 15A / 32V.
    Outputs
  • Voltage: 12VDC and/or 24VDC.
  • Twelve (12) independently controlled fused outputs:
    a) Fail-Safe and/or Fail-Secure power outputs.
    Form “C” Relays rated 28VAC or VDC @ 2.5A.
    b) Auxiliary power outputs (unswitched).
    c) Any combination of the above.
    Outputs Ratings
  • Fuses: 3A/32V.
    Indicators (LED’s)
  • Red LEDs: Outputs are triggered (relays energized).
  • Green LED: FACP disconnect is triggered.

VR6 Voltage Regulator
Input

  • Voltage: 24VDC from eFlow104NB.
    Output
  • Voltage: 12VDC.
  • Current: 6A continuous.
  • Other: Surge suppression.
    Indicators LED
  • Input: 24VDC is present.
  • Output: Powered.
    Two (2) PDS8 Dual Input Power Distribution Modules
    Input
  • Voltage: 12VDC from VR6 and 24VDC from eFlow104NB.
  • Input Fuse: 10A / 32V.
    Outputs
  • Voltage: 12VDC and/or 24VDC.
  • Any of the eight (8) power outputs are selectable to follow power Input 1 or Input 2.
  • Individual outputs may be set to OFF position for s